User Manual
List of parameters
Parameters
1-327
© Siemens AG 2009 - 2013 All Rights Reserved
SINAMICS G120 CU240B/E-2 Control Units List Manual (LH11), 01/2013
Description: Sets the signal source for command 3 for the two-wire control/three-wire control.
Dependency: Refer to: p0015, p3330, p3331, r3333, p3334
Note: The mode of operation of this binector input is dependent on the wire control set in p0015.
Description: Displays the control word for the two wire control/three wire control.
The control signals are dependent on the wire control set in p0015 and the signal states at the digital inputs.
Dependency: Refer to: p0015, p3330, p3331, p3332, p3334
Description: Sets the two wire control/three wire control.
Value: 0: No wire control
1: Two wire control clockwise/counterclockwise 1
2: Two wire control clockwise/counterclockwise 2
3: Three wire control enable clockwise/counterclockwise
4: Three wire control enable ON/reversing
Dependency: Refer to: p0015, p3330, p3331, p3332, r3333
Note: This value depends on the wire control set in p0015.
Description: Compound braking current is used to define the amount of DC current that is produced on stopping the motor dur-
ing U/f operation to further increase the DC brake function.
Compound braking is a superimposition of the DC brake function with regenerative braking (net braking along the
ramp) after OFF1 or OFF3. This permits braking with controlled motor frequency and minimum power input into the
motor. Effective braking without using additional hardware components is obtained by optimizing the ramp down
time and compound braking.
p3332[0...n] BI: 2/3 wire control command 3 / 2/3 wire cmd 3
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0
r3333.0...3 CO/BO: 2/3 wire control control word / 2/3 wire STW
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 ON Yes No -
01 Reversing Yes No -
02 ON/inverting Yes No -
03 Reversing/inverting Yes No -
p3334 2/3 wire control selection / 2/3 wire select
Access level: 4 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 4 0
p3856[0...n] Compound braking current / Compound I_brake
PM240 Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.00 [%] 250.00 [%] 0.00 [%]