Description: Sets the signal source for the enable signal of external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency: Refer to: p2108, p3110, p3112
Refer to: F07862
Description: Sets the signal source for the negated enable signal of external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency: Refer to: p2108, p3110, p3111
Refer to: F07862
Description: Displays the status of NAMUR signal bit bar.
The faults or alarms are assigned to the appropriate signaling/message classes and influence a specific message
bit.
p3111[0...n] BI: External fault 3 enable / Ext fault 3 enab
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 1
p3112[0...n] BI: External fault 3 enable negated / Ext flt 3 enab neg
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0
r3113.0...15 CO/BO: NAMUR message bit bar / NAMUR bit bar
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Fault converter information electron-
ics/SW_error
Yes No -
01 Network fault Yes No -
02 DC link overvoltage Yes No -
03 Fault drive converter power electronics Yes No -
04 Drive converter overtemperature Yes No -
05 Ground fault Yes No -
06 Motor overload Yes No -
07 Bus error Yes No -
08 External safety-relevant shutdown Yes No -
10 Error communication internal Yes No -
11 Fault infeed Yes No -
15 Other faults Yes No -