SINAMICS G120 CU240B/E-2 Control Units List Manual (LH11), 01/2013
Description: Selects faults or alarms for which the message type should be changed.
Dependency: Selects the fault or alarm selection and sets the required type of message realized under the same index.
Refer to: p2119
Notice: It is not possible to re-parameterize the message type in the following cases:
- if there is no existing message number.
Note: Re-parameterization is also possible if a message is present. The change only becomes effective after the mes-
sage has gone.
Description: Sets the message type for the selected fault or alarm.
Value: 1: Fault (F)
2: Alarm (A)
3: No message (N)
Dependency: Selects the fault or alarm selection and sets the required type of message realized under the same index.
Refer to: p2118
Note: Re-parameterization is also possible if a message is present. The change only becomes effective after the mes-
sage has gone.
The message type can only be changed for messages with the appropriate identification.
Example:
F12345(A) --> Fault F12345 can be changed to alarm A12345.
In this case, the message number that may be possibly entered in p2100[0...19] and p2126[0...19] is automatically
removed.
Description: Displays the sum of all of the fault and alarm buffer changes in the drive unit.
Dependency: Refer to: r0944, r2121
Description: This counter is incremented every time the alarm buffer changes.
Dependency: Refer to: r2110, r2122, r2123, r2124, r2125
p2118[0...19] Sets the message number for message type. / Msg_no Msg_type
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 1750, 8075
Min Max Factory setting
0 65535 0
p2119[0...19] Setting the message type / Message type
Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 1750, 8075
Min Max Factory setting
1 3 1
r2120 CO: Sum of fault and alarm buffer changes / Sum buffer changed
Access level: 4 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 8065
Min Max Factory setting
- - -
r2121 CO: Counter alarm buffer changes / Alrm buff changed
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 8065
Min Max Factory setting
- - -