SINAMICS G120 CU240B/E-2 Control Units List Manual (LH11), 01/2013
Description: Sets the communication protocol for the field bus interface.
Value: 0: No protocol
3: PROFIBUS
Notice: For p0014 = 1, the following applies:
After the value has been modified, no further parameter modifications can be made and the status is shown in
r3996. Modifications can be made again when r3996 = 0.
Note: Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
Description: Sets the communication protocol for the field bus interface.
Value: 0: No protocol
1: USS
2: MODBUS
Notice: For p0014 = 1, the following applies:
After the value has been modified, no further parameter modifications can be made and the status is shown in
r3996. Modifications can be made again when r3996 = 0.
Note: Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
Description: Sets the communication protocol for the field bus interface.
Value: 0: No protocol
7: PROFINET
10: Ethernet/IP
Notice: For p0014 = 1, the following applies:
After the value has been modified, no further parameter modifications can be made and the status is shown in
r3996. Modifications can be made again when r3996 = 0.
Note: Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
p2030 Field bus int protocol selection / Field bus protocol
CU240B-2_DP
CU240E-2_DP
CU240E-2_DP_F
Access level: 1 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 3 3
p2030 Field bus int protocol selection / Field bus protocol
CU240B-2
CU240E-2
CU240E-2_F
Access level: 1 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 2 0
p2030 Field bus int protocol selection / Field bus protocol
CU240E-2_PN_F
CU240E-2 PN
Access level: 1 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 10 7