User Manual

Parameters
List of parameters
1-232
© Siemens AG 2009 - 2013 All Rights Reserved
SINAMICS G120 CU240B/E-2 Control Units List Manual (LH11), 01/2013
Description: Displays the effective gain of the integral component of the controller for speed adaptation.
Description: Displays the P component of the controller for speed adaptation.
Description: Displays the I component of the controller for speed adaptation.
Description: Displays estimated (speed) signals of the motor model.
r1773[0]: Displays the estimated (mechanical) slip of the motor model.
r1773[1]: Displays the estimated input speed of the motor model.
Index: [0] = Slip speed estimated
[1] = Speed estimated
Description: Sets the offset voltage in the alpha direction; this compensates the offset voltages of the drive converter/inverter at
low speeds. The value is valid for the rated (nominal) pulse frequency of the power unit.
Note: The value is pre-set during the rotating measurement.
r1768 Motor model speed adaptation Vi effective / MotM n_ada Vi act
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
r1770 CO: Motor model speed adaptation proportional component / MotMod n_adapt Kp
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Units group: 3_1 Unit selection: p0505 Func. diagram: 6730
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
r1771 CO: Motor model speed adaptation I comp. / MotMod n_adapt Tn
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Units group: 3_1 Unit selection: p0505 Func. diagram: 6730
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
r1773[0...1] Motor model slip speed / MotMod slip
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Units group: 3_1 Unit selection: p0505 Func. diagram: -
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
p1774[0...n] Motor model offset voltage compensation alpha / MotMod offs comp A
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
-5.000 [V] 5.000 [V] 0.000 [V]