User Manual
List of parameters
Parameters
1-231
© Siemens AG 2009 - 2013 All Rights Reserved
SINAMICS G120 CU240B/E-2 Control Units List Manual (LH11), 01/2013
Description: Induction motor (ASM):
Displays the referred imaginary system deviation for the adaptation circuit of the motor model.
Permanent magnet synchronous motor (PEM):
Displays the system deviation for speed adaptation.
r1762[0]: Angular deviation [rad-el] of the estimated EMF.
r1762[1]: Angular deviation [rad-el] of the low-level signal response for pulse technique.
Index: [0] = Deviation model 1
[1] = Deviation model 2
Description: Induction motor (ASM):
Displays the referred real system deviation for the adaptation circuit of the motor model.
Permanent magnet synchronous motor (PEM):
Not used.
Description: Sets the proportional gain of the controller for speed adaptation without encoder.
Description: Displays the effective proportional gain of the controller for the speed adaptation.
Description: Sets the integral time of the controller for speed adaptation without encoder
r1762[0...1] Motor model deviation component 1 / MotMod dev comp 1
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 6721, 6730, 6731
Min Max Factory setting
- - -
r1763 Motor model deviation component 2 / MotMod dev comp 2
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
p1764[0...n] Motor model without encoder speed adaptation Kp / MotMod woE n_adaKp
Access level: 4 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6730
Min Max Factory setting
0.000 100000.000 1000.000
r1765 Motor model speed adaptation Kp effective / MotM n_ada Kp act
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
p1767[0...n] Motor model without encoder speed adaptation Tn / MotMod woE n_adaTn
Access level: 4 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6730
Min Max Factory setting
1 [ms] 200 [ms] 4 [ms]