SINAMICS G120 CU240B/E-2 Control Units List Manual (LH11), 01/2013
Description: The programmable characteristic for the U/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the fourth point along the characteristic.
Dependency: Selects the freely programmable characteristic using p1300 = 3.
Refer to: p1310, p1311, p1320, p1321, p1322, p1323, p1324, p1325, p1326
Note: Linear interpolation is carried out between the points 0 Hz/p1310, p1320/p1321 ... p1326/p1327.
The voltage boost when accelerating (p1311) is also applied to the freely programmable U/f characteristic.
Description: Sets the signal source for the voltage setpoint for U/f control with an independent voltage setpoint (p1300 = 19).
Dependency: Selects the U/f control with independent voltage setpoint via p1300 = 19.
Refer to: p1300
Description: Sets the starting frequency at which FCC (Flux Current Control) is activated.
Dependency: The correct operating mode must be set (p1300 = 1, 6).
Warning: An excessively low value can result in instability.
Note: For p1333 = 0 Hz, the FCC starting frequency is automatically set to 6 % of the rated motor frequency.
Description: Sets the starting frequency of the slip compensation.
Note: For p1334 = 0, the starting frequency of the slip compensation is automatically set to 6 % of the rated motor fre-
quency.
p1327[0...n] U/f control programmable characteristic voltage 4 / Uf char U4
Access level: 3 Calculated: p0340 = 1,3 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6300
Min Max Factory setting
0.0 [Vrms] 10000.0 [Vrms] 0.0 [Vrms]
p1330[0...n] CI: U/f control independent voltage setpoint / Uf U_set independ.
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2001 Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 6300
Min Max Factory setting
- - 0
p1333[0...n] U/f control FCC starting frequency / U/f FCC f_start
Access level: 3 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6300
Min Max Factory setting
0.00 [Hz] 3000.00 [Hz] 0.00 [Hz]
p1334[0...n] U/f control slip compensation starting frequency / Slip comp start
Access level: 3 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6310
Min Max Factory setting
0.00 [Hz] 3000.00 [Hz] 0.00 [Hz]