Description: Sets the feedback factor for the ramp-function generator. Its ramp times are decelerated relative to the output signal
of the Vdc_max controller.
Note: For values p1288 = 0.0 to 0.5, the controller dynamics are automatically adapted internally.
Description: Sets the proportional gain for the Vdc controller (DC link voltage controller).
Note: The gain factor is proportional to the capacitance of the DC link.
The parameter is pre-set to a value that is optimally adapted to the capacitance of the power unit.
Description: Sets the integral time for the Vdc controller (DC link voltage controller).
Description: Sets the rate time constant for the Vdc controller (DC link voltage controller).
Description: Sets the output limit for the Vdc min controller (DC link undervoltage controller).
p1288[0...n] Vdc_max controller feedback coupling factor ramp-fct. gen. (U/f) /
Vdc_max factor RFG
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.000 100.000 0.500
p1290[0...n] Vdc controller proportional gain (U/f) / Vdc_ctrl Kp
PM230
PM240
Access level: 3 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6320
Min Max Factory setting
0.00 100.00 1.00
p1291[0...n] Vdc controller integral time (U/f) / Vdc_ctrl Tn
PM230
PM240
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6320
Min Max Factory setting
0 [ms] 10000 [ms] 40 [ms]
p1292[0...n] Vdc controller rate time (U/f) / Vdc_ctrl t_rate
PM230
PM240
Access level: 3 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6320
Min Max Factory setting
0 [ms] 1000 [ms] 10 [ms]
p1293[0...n] Vdc min controller output limit (U/f) / Vdc_min outp_lim
PM240 Access level: 4 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6320
Min Max Factory setting
0.00 [Hz] 600.00 [Hz] 600.00 [Hz]