Description: Sets the signal source for speed setpoint 2 of the speed controller.
Dependency: Refer to: p1155, r1170
Note: For OFF1/OFF3, the ramp-function generator ramp is effective.
The ramp-function generator is set (to the setpoint (r1170)) and stops the drive corresponding to the ramp-down
time (p1121 or p1135). While stopping via the ramp-function generator, STW1.4 is effective (enable ramp-function
generator).
Description: Displays the speed setpoint after the addition of the speed setpoint 1 (p1155) and speed setpoint 2 (p1160).
Dependency: Refer to: p1155, p1160
Note: The value is only correctly displayed at r0899.2 = 1 (operation enabled).
Description: Displays the speed setpoint after selecting the ramp-function generator and adding the speed setpoint 1 (p1155)
and speed setpoint 2 (p1160).
Dependency: Refer to: r1150, p1155, p1160
Description: Displays the number of the selected fixed speed/velocity setpoint.
Dependency: Refer to: p1020, p1021, p1022, p1023
Note: If a fixed speed setpoint has not been selected (p1020 ... p1023 = 0, r1197 = 0), then r1024 = 0 (setpoint = 0).
Description: Displays the control word for the setpoint channel.
p1160[0...n] CI: Speed controller speed setpoint 2 / n_ctrl n_set 2
Access level: 4 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2000 Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 1550, 3080
Min Max Factory setting
- - 0
r1169 CO: Speed controller speed setpoints 1 and 2 / n_ctrl n_set 1/2
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Units group: 3_1 Unit selection: p0505 Func. diagram: 3080
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
r1170 CO: Speed controller setpoint sum / n_ctrl setp sum
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Units group: 3_1 Unit selection: p0505 Func. diagram: 1550, 1590, 1690,
1700, 1750, 3080, 5020, 6030
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
r1197 Fixed speed setpoint number actual / n_set_fixed No act
Access level: 4 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 3010
Min Max Factory setting
- - -
r1198.0...15 CO/BO: Control word setpoint channel / STW setpoint chan
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 1530, 2505
Min Max Factory setting
- - -