User Manual

Parameters
List of parameters
1-160
© Siemens AG 2009 - 2013 All Rights Reserved
SINAMICS G120 CU240B/E-2 Control Units List Manual (LH11), 01/2013
Description: Sets the initial rounding-off time for OFF3 for the extended ramp generator.
Description: Sets the initial rounding-off time for OFF3 for the extended ramp generator.
Description: Sets the final rounding-off time for OFF3 for the extended ramp generator.
Description: Sets the signal source for scaling the up ramp.
Dependency: Refer to: p1120
Note: The ramp-up time is set in p1120.
Description: Sets the signal source for scaling the down ramp.
Dependency: Refer to: p1121
Note: The ramp-down time is set in p1121.
p1136[0...n] OFF3 initial rounding-off time / RFGOFF3 t_strt_rnd
PM230 Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 3070
Min Max Factory setting
0.000 [s] 30.000 [s] 2.000 [s]
p1136[0...n] OFF3 initial rounding-off time / RFGOFF3 t_strt_rnd
PM240
PM250, PM260
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 3070
Min Max Factory setting
0.000 [s] 30.000 [s] 0.000 [s]
p1137[0...n] OFF3 final rounding-off time / RFG OFF3 t_end_del
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 3070
Min Max Factory setting
0.000 [s] 30.000 [s] 0.000 [s]
p1138[0...n] CI: Up ramp scaling / Up ramp scaling
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: PERCENT Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 3060, 3070
Min Max Factory setting
- - 1
p1139[0...n] CI: Down ramp scaling / Down ramp scaling
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: PERCENT Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 3060, 3070
Min Max Factory setting
- - 1