Description: Sets the signal source to invert the setpoint.
Dependency: Refer to: r1198
Caution: If the technology controller is being used as the speed main setpoint (p2251 = 0), do not invert the setpoint using
p1113 when the technology controller is enabled because this can cause the speed to change suddenly and lead to
positive couplings in the control loop.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source to invert the setpoint.
Dependency: Refer to: r1198
Caution: If the technology controller is being used as the speed main setpoint (p2251 = 0), do not invert the setpoint using
p1113 when the technology controller is enabled because this can cause the speed to change suddenly and lead to
positive couplings in the control loop.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Displays the speed/velocity setpoint after the changeover and limiting the direction.
Description: Sets the ramp-function generator type.
p1113[0...n] BI: Setpoint inversion / Setp inv
CU240B-2_DP
CU240E-2_DP
CU240E-2_DP_F
CU240E-2_PN_F
CU240E-2 PN
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2441, 2442, 2505,
3040
Min Max Factory setting
- - [0] 2090.11
[1] 0
[2] 0
[3] 0
p1113[0...n] BI: Setpoint inversion / Setp inv
CU240B-2
CU240E-2
CU240E-2_F
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2441, 2442, 2505,
3040
Min Max Factory setting
- - [0] 722.1
[1] 0
[2] 0
[3] 0
r1114 CO: Setpoint after the direction limiting / Setp after limit
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Units group: 3_1 Unit selection: p0505 Func. diagram: 1550, 3040, 3050
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
p1115 Ramp-function generator selection / RFG selection
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 1550, 3080
Min Max Factory setting
0 1 1