Description: Sets the signal source to continually increase the setpoint for the motorized potentiometer.
The setpoint change (CO: r1050) depends on the set ramp-up time (p1047) and the duration of the signal that is
present (BI: p1035).
Dependency: Refer to: p1036
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source to continually increase the setpoint for the motorized potentiometer.
The setpoint change (CO: r1050) depends on the set ramp-up time (p1047) and the duration of the signal that is
present (BI: p1035).
Dependency: Refer to: p1036
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source to continuously lower the setpoint for the motorized potentiometer.
The setpoint change (CO: r1050) depends on the set ramp-down time (p1048) and the duration of the signal that is
present (BI: p1036).
Dependency: Refer to: p1035
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1035[0...n] BI: Motorized potentiometer setpoint raise / Mop raise
CU240B-2_DP
CU240E-2_DP
CU240E-2_DP_F
CU240E-2_PN_F
CU240E-2 PN
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2505, 3020
Min Max Factory setting
- - [0] 2090.13
[1] 0
[2] 0
[3] 0
p1035[0...n] BI: Motorized potentiometer setpoint raise / Mop raise
CU240B-2
CU240E-2
CU240E-2_F
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2505, 3020
Min Max Factory setting
- - 0
p1036[0...n] BI: Motorized potentiometer lower setpoint / Mop lower
CU240B-2_DP
CU240E-2_DP
CU240E-2_DP_F
CU240E-2_PN_F
CU240E-2 PN
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2505, 3020
Min Max Factory setting
- - [0] 2090.14
[1] 0
[2] 0
[3] 0