Changeable
The "-" sign indicates that the parameter can be changed in any object state and
that the change will be effective immediately.
The information "C(x), T, U" ((x): optional) means that the parameter can be
changed only in the specified drive unit state and that the change will not take
effect until the unit switches to another state. One or more states are possible.
The following states may be specified:
Scaling
Specification of the reference variable with which a signal value is automatically
converted for a BICO interconnection.
The following reference variables are available:
• p2000 ... p2006: Reference speed, reference voltage, etc.
• PERCENT: 1.0 = 100 %
• 4000H: 4000 hex = 100 %
• C(x) Commissioning C: Commissioning
Drive commissioning is in progress (p0010 > 0).
Pulses cannot be enabled.
The parameter can only be changed in the following drive commission-
ing settings (p0010 > 0):
C: Changeable for all settings p0010 > 0.
C(x): Only changeable when p0010 = x.
A modified parameter value does not take effect until the device com-
missioning mode is exited with p0010 = 0.
• U Operation U: Run
Pulses are enabled.
• T Ready T: Ready to run
The pulses are not enabled and the status "C(x)" is not active.