List of parameters
Parameters
1-125
© Siemens AG 2009 - 2013 All Rights Reserved
SINAMICS G120 CU240B/E-2 Control Units List Manual (LH11), 01/2013
Dependency: The fault buffer is deleted (cleared) by setting p0952 to 0.
Refer to: r0945, r0947, r0948, r0949, r2109, r2130, r2133, r2136
Description: Displays the corresponding value for the PROFIBUS baud rate.
Value: 0: 9.6 kbit/s
1: 19.2 kbit/s
2: 93.75 kbit/s
3: 187.5 kbit/s
4: 500 kbit/s
6: 1.5 Mbit/s
7: 3 Mbit/s
8: 6 Mbit/s
9: 12 Mbit/s
10: 31.25 kbit/s
11: 45.45 kbit/s
255: Unknown
Description: Displays the device identification.
Index: [0] = Company (Siemens = 42)
[1] = Device type
[2] = Firmware version
[3] = Firmware date (year)
[4] = Firmware date (day/month)
[5] = Number of drive objects
[6] = Firmware patch/hot fix
Note: Example:
r0964[0] = 42 --> SIEMENS
r0964[1] = device type, see below
r0964[2] = 403 --> first part of the firmware version V04.03 (for second part, refer to index 6)
r0964[3] = 2010 --> year 2010
r0964[4] = 1705 --> 17th of May
r0964[5] = 1 --> 1 drive object
r0964[6] = 200 --> second part, firmware version (complete version: V04.03.02.00)
Device type:
r0964[1] = 6100 --> SINAMICS G120 CU240B-2_DP
r0964[1] = 6103 --> SINAMICS G120 CU240B-2
r0964[1] = 6210 --> SINAMICS G120 CU240E-2_DP
r0964[1] = 6211 --> SINAMICS G120 CU240E-2_PN
r0964[1] = 6213 --> SINAMICS G120 CU240E-2
r0964[1] = 6220 --> SINAMICS G120 CU240E-2_DP_F
r0964[1] = 6221 --> SINAMICS G120 CU240E-2_PN_F
r0964[1] = 6223 --> SINAMICS G120 CU240E-2_F
r0963 PROFIBUS baud rate / PB baud rate
CU240B-2_DP
CU240E-2_DP
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 255 -
r0964[0...6] Device identification / Device ident.
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -