User Manual
List of parameters
Parameters
1-121
© Siemens AG 2009 - 2013 All Rights Reserved
SINAMICS G120 CU240B/E-2 Control Units List Manual (LH11), 01/2013
Description: Displays the status and control words of the drive coupling.
Note: Re bit 01:
Bit 1 is used to control an external line contactor.
Description: Sets the signal source to select the "parking axis" function.
Dependency: BI: p0897 = 0 signal
The function "parking axis" is not selected.
BI: p0897 = 1 signal
The function "parking axis" is selected.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: After it has been selected the "parking axis" function only becomes active when the pulses are suppressed.
Description: Displays the control word of the sequence control.
Note: OC: Operating condition
Re bit 10:
If p0700 = 2 is set, bit 10 always shows "1".
r0863.1 CO/BO: Drive coupling status word/control word / CoupleZSW/STW
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
01 Energize contactor Yes No -
p0897 BI: Parking axis selection / Parking axis sel
Access level: 2 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0
r0898.0...14 CO/BO: Control word sequence control / STW seq_ctrl
Access level: 2 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 1530, 2501
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 ON/OFF1 Yes No -
01 OC / OFF2 Yes No -
02 OC / OFF3 Yes No -
03 Operation enable Yes No -
04 Ramp-function generator enable Yes No -
05 Continue ramp-function generator Yes No -
06 Speed setpoint enable Yes No -
07 Command open brake Yes No -
08 Jog 1 Yes No -
09 Jog 2 Yes No -
10 Master ctrl by PLC Yes No -
12 Speed controller enable Yes No -
14 Command close brake Yes No -