Technical data
CU230P-2 Control Units, Getting Started
A5E02484096, 05/2009
23
Commissioning with the IOP
For commissioning, the IOP must either be directly plugged onto the Control Unit
of the inverter or must be connected to it via the handheld enclosure. This
therefore establishes all of the connections required.
Plug the IOP onto the inverter
After you have connected-up the Control Unit, locate the lower edge of the IOP,
as shown in the diagram, onto the protruding lower section of the Control Unit
(①) and snap the IOP (②) onto the Control Unit.
Removing the IOP from the inverter
By pressing the interlocking knob (③), you release the mechanical connection to
the control module (Control Unit) and you can then remove the IOP.
The IOP can be inserted and removed also under voltage without any
restrictions.
Prerequisites for commissioning using the IOP
● The IOP is plugged onto the inverter.
● The inverter power supply has been switched on.
4.3.1 Commissioning with the IOP
Description
When you plug the IOP onto the inverter for the first time, then it logs-on with the English welcome screen and then goes
into the language selection menu.
Using the navigation wheel, select the language that you wish to use and acknowledge this by briefly pressing (OK or accept
function). The IOP then changes into the status display (standard display of the IOP).
For commissioning, select the Wizards using the navigation wheel and acknowledge with OK.
For basic commissioning, you can select one of the following Wizards using the navigation wheel:
● Basic commissioning
General basic commissioning
● Open-loop controlled fan
Basic commissioning for a fan without control loop
● Closed-loop controlled fan
Basic commissioning for a fan with control loop
● Open-loop controlled pump
Basic commissioning for a pump without control loop
● Closed-loop controlled pump
Basic commissioning for a pump with control loop
● Open-loop controlled compressor
Basic commissioning for a compressor without control loop
● Closed-loop controlled compressor
Basic commissioning for a compressor with control loop
● Roller conveyor
Basic commissioning for roller conveyors