Technical data

CU230P-2 Control Units, Getting Started
20 A5E02484096, 05/2009
4.1.6 Carrying out commissioning
Description
The Commissioning Wizard starts
with the screen form to set the
closed-loop control. Using the drop-
down menu, select one of the listed
open-loop or closed-loop control
types and click on "Continue".
Screen forms then follow one after the other for
Setpoint and command sources
Note: For CU230P-2 DP CUs, the PROFIdrive telegram must be changed to 999 before the command and setpoint
sources can be changed.
Motor type
Motor data
Drive functions
For the drive functions, the motor data identification type can be selected. We recommend that the motor data
identification is always carried out with the motor at a standstill. Whether the rotating measurement can be carried out
depends on the application (e.g. direction of rotation, distance limits) and must be decided depending on the particular
plant.
The motor data identification starts with the first ON command after commissioning.
Important parameters (e.g. max. and min. speed or ramp-up and ramp-down time)
Calculating the motor data
Summary
This screen form allows the settings that have been made to be permanently saved in the inverter
(
) and in addition, to save them in a text file via the buffer. The device configuration is
completed with "Finish".