Fig. 3-173 8075 – Faults/alarms configuration
- 8075 -
Function diagram
87654321
fp_8075_97_51.vsd
Diagnostics
G120 CU230P-2
13.03.2018 V4.7_10
Faults/alarms configuration
[0]
[1]
[19]
[0]
[1]
[19]
[0]
[1]
[19]
[0]
[1]
[19]
[0]
[1]
[19]
[0]
[1]
[19]
Changing the fault response for maximum 20 faults <1> Changing the message type - fault => alarm for maximum 20 faults/alarms <1>
Changing the acknowledge mode for maximum 20 faults <1>
0. Fault code
1. Fault code
19. Fault code
Fault response
Fault response
Fault response
0. Fault code
1. Fault code
19. Fault code
0 = NONE
1 = OFF1
2 = OFF2
3 = OFF3
5 = STOP2
6 = IASC/DCBRK
0. Fault/alarm code
1. Fault/alarm code
19. Fault/alarm code
Fault/alarm type
Fault/alarm type
Fault/alarm type
1 = Fault
2 = Alarm
3 = No message
Acknowledge mode
Acknowledge mode
Acknowledge mode
1 = Acknowledgment is only possible using POWER ON
2 = Acknowledgment IMMEDIATELY after the cause has been removed.
Chng resp F_no
0 ... 65535
p2100 (0)
Chng resp resp
0 ... 6
p2101 (0)
Chng type msg_no
0 ... 65535
p2118 (0)
Change type type
1 ... 3
p2119 (1)
Chng ackn F_no
0 ... 65535
p2126 (0)
Chng ackn mode
1 ... 2
p2127 (1)
The fault response, acknowledge mode and message type for all faults and alarms are set to meaningful default values in the factory setting.
Changes are only possible in specific value ranges specified by SIEMENS.
When the message type is changed, the supplementary information is tranferred from fault value r0949 to alarm value r2124 and vice versa.
<1>
DCBRK = DC Brake
IASC = Internal Armature Short-Circuit