User Manual
SINAMICS G120 CU230P-2 Control Units
List Manual, 04/2018, A5E33838102
567
3 Function diagrams
3.3 Input/output terminals
Fig. 3-9 2252 – Analog input 2 (AI 2)
- 2252 -
Function diagram
87654321
fp_2252_97_01.vsd
Input/Output Terminals
G120 CU230P-2
13.03.2018 V4.7_10
Analog input 2 (AI 2)
3
3
20 mA
T0
0 … 20 mA
°C
Kl. 50
[%]
xy
<2> <2>
A
D
+
-
<1>
<1>
x
1
y
2
x
2
y
1
y
x
[%]
y
x
2
x
1
<2>
AI 2 TEMP ĸĺ I
1
0
20 mA
1
0
Current
Hardware smoothing
100 µs
Scaling
Notice:
The voltage between inputs and between input and the ground point must not exceed 35 V.
When the load resistor is switched in (DIP switch in position ĺI), the voltage between the input terminals
must not exceed 10 V or the impressed current 80 mA. If this is not observed the input will be damaged.
For p0756 = 2, 3 the units are mA.
For p0756 = 6, 7, 10 the units are °C.
F03505
"Wire breakage"
CU wire brk t_del
0 ... 1000 [ms]
p0762 (100)
CU AI sim_mode
0 ... 1
p0797 (0)
CU AI type
0 ... 10
p0756 (4)
CU WireBrkThresh
0.00 ... 20.00
p0761 (2.00)
CU AI T_smooth
0.0 ... 1000.0 [ms]
p0753 (0.0)
CU AI sim setp
-50.000 ... 2000.000
p0798 (0.000)
CU AI char y1
-1000.00 ... 1000.00 [%]
p0758 (0.00)
CU AI char y2
-1000.00 ... 1000.00 [%]
p0760 (100.00)
CU AI char x1
-50.000 ... 160.000
p0757 (0.000)
CU AI char x2
-50.000 ... 160.000
p0759 (10.000)
CU AI sim_mode
0 ... 1
p0797 (0)
Kl. 51
Kl. = Terminal
Sampling time of the AI: 4 ms
r0755
CU AI value in % [%]
[2]
LG-Ni1000
PT1000
°C
LG-Ni1000/PT1000/DIN Ni 1k (6180 ppm / K)
<3> Wire breakage sensing only activated when p0756 = 3.
<2>
<3>
<2>
Type switching
Analog input
I
GND
[2] (0)
[2] (2)
[2] (0.00) [2] (100)
[2] (0)
[2] (0.00)
[2] (0.00)
[2] (0.00)
[2] (0.00)
[2] (0.00)
[2] (0.00)
CU AI status word
r0751
r0752
CU AI U/I_inp act
[2]
Reference
quantities
<2>
[7033.5]
[7033.4]
x
x
1
· x
2
100 %