SINAMICS G120 CU230P-2 Control Units
List Manual, 04/2018, A5E33838102
451
2 Parameters
2.2 List of parameters
Description: Sets the lower limit for the actual value signal of the free technology controller 2.
Dependency: Refer to: p11264
Description: Sets the inversion of the actual value signal of the free technology controller 2.
Value: 0: No inversion
1: Inversion
Description: Display and connector output for the actual value after the limiter of the free technology controller 2.
Description: Display and connector output for the system deviation of the free technology controller 2.
Description: Sets the time constant for the differentiation (D component) of the free technology controller 2.
Note: Value = 0: Differentiation is deactivated.
Description: Sets the proportional gain (P component) of the free technology controller 2.
Note: Value = 0: The proportional gain is deactivated.
p11268 Free tec_ctrl 2 actual value lower limit / Ftec2 act v lo lim
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Unit group: 9_4 Unit selection: p11226 Func. diagram: 7030
Min Max Factory setting
-200.00 [%] 200.00 [%] -100.00 [%]
p11271 Free tec_ctrl 2 actual value inversion / Ftec2 act v inv
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
0 1 0
r11272 CO: Free tec_ctrl 2 actual value after limiter / Ftec2 act v af lim
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Unit group: 9_4 Unit selection: p11226 Func. diagram: 7030
Min Max Factory setting
- [%] - [%] - [%]
r11273 CO: Free tec_ctrl 2 system deviation / Ftec2 sys dev
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Unit group: 9_4 Unit selection: p11226 Func. diagram: 7030
Min Max Factory setting
- [%] - [%] - [%]
p11274 Free tec_ctrl 2 differentiation time constant / Ftec2 D comp T
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
0.000 [s] 60.000 [s] 0.000 [s]
p11280 Free tec_ctrl 2 proportional gain / Ftec2 Kp
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
0.000 1000.000 1.000