2 Parameters
2.2 List of parameters
Description: Display and connector output for the actual value after the limiter of the free technology controller 1.
Description: Display and connector output for the system deviation of the free technology controller 1.
Description: Sets the time constant for the differentiation (D component) of the free technology controller 1.
Note: Value = 0: Differentiation is deactivated.
Description: Sets the proportional gain (P component) of the free technology controller 1.
Note: Value = 0: The proportional gain is deactivated.
Description: Sets the integral time (I component, integrating time constant) of the free technology controller 1.
Note: Value = 0: The integral time is disabled.
If the parameter is set to zero during operation, the I component retains its most recent value.
r11172 CO: Free tec_ctrl 1 actual value after limiter / Ftec1 act v af lim
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Unit group: 9_3 Unit selection: p11126 Func. diagram: 7030
Min Max Factory setting
- [%] - [%] - [%]
r11173 CO: Free tec_ctrl 1 system deviation / Ftec1 sys dev
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Unit group: 9_3 Unit selection: p11126 Func. diagram: 7030
Min Max Factory setting
- [%] - [%] - [%]
p11174 Free tec_ctrl 1 differentiation time constant / Ftec1 D comp T
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
0.000 [s] 60.000 [s] 0.000 [s]
p11180 Free tec_ctrl 1 proportional gain / Ftec1 Kp
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
0.000 1000.000 1.000
p11185 Free tec_ctrl 1 integral time / Ftec1 Tn
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
0.000 [s] 10000.000 [s] 30.000 [s]