2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
438 List Manual, 04/2018, A5E33838102
Description: Sets the signal source for the actual value of the free technology controller 0.
Description: Sets the smoothing time constant (PT1) for the actual value of the free technology controller 0.
Description: Sets the upper limit for the actual value signal of the free technology controller 0.
Dependency: Refer to: p11064
Description: Sets the lower limit for the actual value signal of the free technology controller 0.
Dependency: Refer to: p11064
Description: Sets the inversion of the actual value signal of the free technology controller 0.
Value: 0: No inversion
1: Inversion
Description: Display and connector output for the actual value after the limiter of the free technology controller 0.
p11064 CI: Free tec_ctrl 0 actual value signal source / Ftec0 act v s_s
Access level: 2 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
- - 0
p11065 Free tec_ctrl 0 actual value smoothing time constant / Ftec0 act v T
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
0.00 [s] 60.00 [s] 0.00 [s]
p11067 Free tec_ctrl 0 actual value upper limit / Ftec0 act v up lim
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Unit group: 9_2 Unit selection: p11026 Func. diagram: 7030
Min Max Factory setting
-200.00 [%] 200.00 [%] 100.00 [%]
p11068 Free tec_ctrl 0 actual value lower limit / Ftec0 act v lo lim
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Unit group: 9_2 Unit selection: p11026 Func. diagram: 7030
Min Max Factory setting
-200.00 [%] 200.00 [%] -100.00 [%]
p11071 Free tec_ctrl 0 actual value inversion / Ftec0 act v inv
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
0 1 0
r11072 CO: Free tec_ctrl 0 actual value after limiter / Ftec0 act v af lim
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Unit group: 9_2 Unit selection: p11026 Func. diagram: 7030
Min Max Factory setting
- [%] - [%] - [%]