2 Parameters
2.2 List of parameters
Description: Displays the actual system deviation of the speed controller.
Description: Displays the slip frequency for induction motors (ASM).
Description: Display and connector output for the unsmoothed output frequency of the power unit.
Frequency components from the slip compensation (induction motor) are included.
Dependency: Refer to: r0024
Note: The output frequency is available smoothed (r0024) and unsmoothed (r0066).
Description: Display and connector output for the maximum output current of the power unit.
Dependency: The maximum output current is determined by the parameterized current limit and the motor and converter thermal
protection.
Refer to: p0290, p0640
Description: Displays actual absolute current.
Index: [0] = Unsmoothed
[1] = Smoothed with p0045
Dependency: Refer to: r0027
Notice: The value is updated with the current controller sampling time.
r0064 CO: Speed controller system deviation / n_ctrl sys dev
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Unit group: 3_1 Unit selection: p0505 Func. diagram: 6040, 6824
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
r0065 Slip frequency / f_Slip
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Unit group: 2_1 Unit selection: p0505 Func. diagram: 6310, 6700, 6727,
6730, 6732
Min Max Factory setting
- [Hz] - [Hz] - [Hz]
r0066 CO: Output frequency / f_outp
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Unit group: 2_1 Unit selection: p0505 Func. diagram: 6730, 6731, 6792,
6799, 6841, 6842, 6843
Min Max Factory setting
- [Hz] - [Hz] - [Hz]
r0067 CO: Output current maximum / Current max
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2002 Dyn. index: -
Unit group: 6_2 Unit selection: p0505 Func. diagram: 6300, 6640, 6724,
6828, 6850
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
r0068[0...1] CO: Absolute current actual value / I_act abs val
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2002 Dyn. index: -
Unit group: 6_2 Unit selection: p0505 Func. diagram: 6300, 6714, 6799,
7017, 8017, 8021, 8022
Min Max Factory setting
- [Arms] - [Arms] - [Arms]