User Manual
SINAMICS G120 CU230P-2 Control Units
List Manual, 04/2018, A5E33838102
427
2 Parameters
2.2 List of parameters
Notice: When the DHCP mode is active (parameter value not equal to 0), PROFINET communication via this interface is no
longer possible! However, the interface can be used for commissioning tool such as STARTER or SCOUT.
Description: Displays the MAC address for the onboard PROFINET interface on the Control Unit.
Description: Displays the PROFINET Device Access Point ID (DAP ID) for the onboard PROFINET interface.
The combination of device ID (r8909) and DAP ID uniquely identifies a PROFINET access point.
Note: List of the SINAMICS DAP IDs:
20007 hex: CBE20 V4.5
20008 hex: CBE20 V4.6
20107 hex: CU310-2 PN V4.5
20108 hex: CU310-2 PN V4.6
20307 hex: CU320-2 PN V4.5
20308 hex: CU320-2 PN V4.6
20407 hex: CU230P-2 PN /CU240x-2 PN V4.5
20408 hex: CU230P-2 PN /CU240x-2 PN /CU250S-2 PN /G110M PN V4.6
20507 hex: CU250D-2 PN V4.5
20508 hex: CU250D-2 PN V4.6
Description: Sets the profile for Ethernet/IP.
Value: 0: SINAMICS
1: ODVA AC/DC
Note: Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
ODVA: Open DeviceNet Vendor Association
Description: Sets the STOP mode for the Ethernet/IP ODVA profile (p8980 = 1).
Value: 0: OFF1
1: OFF2
Dependency: Refer to: p8980
r8935[0...5] PN MAC address / PN MAC addr
CU230P-2_PN Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0000 hex 00FF hex -
r8939 PN DAP ID / PN DAP ID
CU230P-2_PN Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
p8980 Ethernet/IP profile / Eth/IP profile
CU230P-2_PN Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2473
Min Max Factory setting
0 1 0
p8981 Ethernet/IP ODVA STOP mode / Eth/IP ODVA STOP
CU230P-2_PN Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2473
Min Max Factory setting
0 1 0