User Manual

SINAMICS G120 CU230P-2 Control Units
List Manual, 04/2018, A5E33838102
39
2 Parameters
2.2 List of parameters
Note: For bit 03:
This signal is inverted if it is interconnected to a digital output.
For r0052:
The status bits have the following sources:
Bit 00: r0899 Bit 0
Bit 01: r0899 Bit 1
Bit 02: r0899 Bit 2
Bit 03: r2139 Bit 3 (or r1214.10 for p1210 > 0)
Bit 04: r0899 Bit 4
Bit 05: r0899 Bit 5
Bit 06: r0899 Bit 6
Bit 07: r2139 Bit 7
Bit 08: r2197 Bit 7
Bit 09: r0899 Bit 7
Bit 10: r2197 Bit 6
Bit 11: r0056 Bit 13 (negated)
Bit 13: r2135 Bit 14 (negated)
Bit 14: r2197 Bit 3
Bit 15: r2135 Bit 15 (negated)
Description: Display and BICO output for status word 2.
Notice: p2081 is used to define the signal sources of the PROFIdrive status word interconnection.
Note: The following status bits are displayed in r0053:
Bit 00: r1239 Bit 8
Bit 01: r2197 Bit 5 (negated)
Bit 02: r2197 Bit 0 (negated)
Bit 03: r2197 Bit 8
Bit 04: r2197 Bit 2
Bit 05: r2197 Bit 1
Bit 06: r2197 Bit 4
Bit 07: r2197 Bit 9
Bit 08: r2197 Bit 10
Bit 09: r1199 Bit 2 (negated)
Bit 10: r2349 Bit 10
Bit 11: r2349 Bit 11
r0053.0...11 CO/BO: Status word 2 / ZSW 2
Access level: 2 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 DC braking active Yes No -
01 |n_act| > p1226 (n_standstill) Yes No -
02 |n_act| > p1080 (n_min) Yes No -
03 I_act >= p2170 Yes No -
04 |n_act| > p2155 Yes No -
05 |n_act| <= p2155 Yes No -
06 |n_act| >= r1119 (n_set) Yes No -
07 Vdc <= p2172 Yes No -
08 Vdc > p2172 Yes No -
09 Ramp-up/ramp-down completed Yes No -
10 Technology controller output at the lower
limit
Yes No -
11 Technology controller output at the upper
limit
Yes No -