User Manual
2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
332 List Manual, 04/2018, A5E33838102
Description: Sets the signal source to hold the integrator for the technology controller.
Description: Sets the signal source for the precontrol signal of the technology controller.
Description: Sets the signal source to enable the technology controller output.
The technology controller output is enabled with a 1 signal.
The technology controller output is held with a 0 signal.
Description: Sets the maximum limit of the technology controller.
Dependency: Refer to: p2292
Caution: The maximum limit must always be greater than the minimum limit (p2291 > p2292).
Description: Sets the minimum limit of the technology controller.
Dependency: Refer to: p2291
Caution: The maximum limit must always be greater than the minimum limit (p2291 > p2292).
p2286[0...n] BI: Hold technology controller integrator / Tec_ctr integ hold
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
- - 56.13
p2289[0...n] CI: Technology controller precontrol signal / Tec_ctr prectr_sig
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
- - 0
p2290[0...n] BI: Technology controller limiting enable / Tec_ctrl lim enab
Access level: 2 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
- - 1
p2291 CO: Technology controller maximum limiting / Tec_ctrl max_lim
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
-200.00 [%] 200.00 [%] 100.00 [%]
p2292 CO: Technology controller minimum limiting / Tec_ctrl min_lim
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
-200.00 [%] 200.00 [%] 0.00 [%]