SINAMICS G120 CU230P-2 Control Units
298 List Manual, 04/2018, A5E33838102
Description: Sets the signal source for external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency: Refer to: p3110, p3111, p3112
Refer to: F07862
Note: An external fault is triggered with a 1/0 signal.
Description: Displays the system runtime in milliseconds when the fault was removed.
Dependency: Refer to: r0945, r0947, r0948, r0949, r2130, r2133, r2136, p8400
Notice: The time comprises r2136 (days) and r2109 (milliseconds).
Note: The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the fault buffer and the assignment of the indices is shown in r0945.
Description: This parameter is identical to r2122.
Description: Number of alarms that have occurred after the last reset.
Dependency: When p2111 is set to 0, the following is initiated:
- all of the alarms of the alarm buffer that have gone [0...7] are transferred into the alarm history [8...63].
- the alarm buffer [0...7] is deleted.
Refer to: r2110, r2122, r2123, r2124, r2125
Note: The parameter is reset to 0 at POWER ON.
p2108[0...n] BI: External fault 3 / External fault 3
PM330 Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 2546
Min Max Factory setting
- - 4022.1
r2109[0...63] Fault time removed in milliseconds / t_flt resolved ms
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 8050, 8060
Min Max Factory setting
- [ms] - [ms] - [ms]
r2110[0...63] Alarm number / Alarm number
Access level: 2 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 8065
Min Max Factory setting
- - -
p2111 Alarm counter / Alarm counter
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 8050, 8065
Min Max Factory setting
0 65535 0