User Manual

2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
280 List Manual, 04/2018, A5E33838102
Description: Connector output to interconnect PZD (setpoints) with word format received from the fieldbus controller.
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
Notice: Where there is a multiple interconnection of a connector output, all the connector inputs must either have Integer or
FloatingPoint data types. A BICO interconnection for a single PZD can only take place either on r2050 or r2060.
Description: Selects the PZD (actual values) with word format to be sent to the fieldbus controller.
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
[12] = PZD 13
[13] = PZD 14
[14] = PZD 15
[15] = PZD 16
[16] = PZD 17
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
r2050[0...11] CO: PROFIdrive PZD receive word / PZD recv word
Access level: 3 Calculated: - Data type: Integer16
Can be changed: - Scaling: 4000H Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2440, 2468, 9360
Min Max Factory setting
- - -
p2051[0...16] CI: PROFIdrive PZD send word / PZD send word
CU230P-2_DP
CU230P-2_PN
Access level: 3 Calculated: - Data type: U32 / Integer16
Can be changed: U, T Scaling: 4000H Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2450, 2470, 9370
Min Max Factory setting
- - [0] 2089[0]
[1] 63[0]
[2...16] 0