User Manual

SINAMICS G120 CU230P-2 Control Units
List Manual, 04/2018, A5E33838102
251
2 Parameters
2.2 List of parameters
Description: Sets the configuration for the modulator.
Notice: Bit 1 = 1 can only be set under a pulse inhibit and for r0192.14 = 1.
Note: For bit 00 = 0:
Voltage limitation from the minimum of the DC link voltage (lower ripple in the output current, reduced output
voltage).
For bit 00 = 1:
Voltage limitation from averaged DC link voltage (higher output voltage with increased ripple in the output current).
The selection is only valid if the DC link compensation is not performed in the Control Unit (bit 1 = 0).
For bit 01 = 0:
DC link voltage compensation in the modulator.
For bit 01 = 1:
DC link voltage compensation in the current control.
Description: Sets the configuration for the modulator.
Notice: Bit 1 = 1 can only be set under a pulse inhibit and for r0192.14 = 1.
Note: For bit 00 = 0:
Voltage limitation from the minimum of the DC link voltage (lower ripple in the output current, reduced output
voltage).
For bit 00 = 1:
Voltage limitation from averaged DC link voltage (higher output voltage with increased ripple in the output current).
The selection is only valid if the DC link compensation is not performed in the Control Unit (bit 1 = 0).
For bit 01 = 0:
DC link voltage compensation in the modulator.
For bit 01 = 1:
DC link voltage compensation in the current control.
p1810 Modulator configuration / Modulator config
PM230
PM250, PM260
Access level: 4 Calculated: - Data type: Unsigned16
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Avg value filter for V_lim (only for
Vdc_comp in modulator)
Yes No -
01 DC link voltage compensation in the current
control
Yes No -
p1810 Modulator configuration / Modulator config
PM240 Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Avg value filter for V_lim (only for
Vdc_comp in modulator)
Yes No -
01 DC link voltage compensation in the current
control
Yes No -