226 List Manual, 04/2018, A5E33838102
Description: Sets a dynamic voltage reserve.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p0500
Note: In the field weakening range, it must be expected that the control dynamic performance is somewhat restricted due to
the limited possibilities of controlling/adjusting the voltage. This can be improved by increasing the voltage reserve.
Increasing the reserve reduces the steady-state maximum output voltage (r0071).
Description: Sets a dynamic voltage reserve.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p0500
Note: In the field weakening range, it must be expected that the control dynamic performance is somewhat restricted due to
the limited possibilities of controlling/adjusting the voltage. This can be improved by increasing the voltage reserve.
Increasing the reserve reduces the steady-state maximum output voltage (r0071).
Description: Sets the limit of the voltage target value.
In steady-state field weakening operation this corresponds to the required output voltage.
The value of 100% refers to p0304.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Note: The output voltage is only limited if the maximum output voltage (r0071) minus the voltage reserve (p1574)
corresponds to a value higher than p1575.
Limiting via p1575 allows the influence of the voltage ripple of the line supply voltage to be eliminated at the operating
point.
Description: The following applies for a synchronous reluctance motor:
Sets the time constant for reducing the flux setpoint for a load-dependent optimum flux characteristic.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p1579
p1574[0...n] Voltage reserve dynamic / U_reserve dyn
PM230
PM330
Access level: 3 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: 5_1 Unit selection: p0505 Func. diagram: 6723, 6724
Min Max Factory setting
0.0 [Vrms] 150.0 [Vrms] 2.0 [Vrms]
p1574[0...n] Voltage reserve dynamic / U_reserve dyn
PM240
PM250, PM260
Access level: 3 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: 5_1 Unit selection: p0505 Func. diagram: 6723, 6724
Min Max Factory setting
0.0 [Vrms] 150.0 [Vrms] 10.0 [Vrms]
p1575[0...n] Voltage target value limit / U_tgt val lim
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6725
Min Max Factory setting
50.00 [%] 300.00 [%] 200.00 [%]
p1578[0...n] Flux reduction flux decrease time constant / Flux red dec T
Access level: 3 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6791
Min Max Factory setting
20 [ms] 5000 [ms] 200 [ms]