User Manual
SINAMICS G120 CU230P-2 Control Units
List Manual, 04/2018, A5E33838102
193
2 Parameters
2.2 List of parameters
Description: Sets the delay time to switch back to converter operation for a non-synchronized bypass.
Dependency: The "Bypass" function is only available for induction motors.
Description: Sets the delay time for switching to line operation for a non-synchronized bypass.
Dependency: The "Bypass" function is only available for induction motors.
Description: Sets the speed threshold to activate the bypass.
Dependency: The "Bypass" function is only available for induction motors.
If the drive setpoint speed is entered via a motorized potentiometer, then the configuration bit p1030.4 should be set
in order to ensure the bypass via speed threshold function.
Note: When selecting p1260 = 3 and p1267.1 = 1, the bypass is automatically activated when this speed is reached.
The bypass speed threshold is only effective for positive directions of rotation. If the drive connected to the line
supply requires negative speeds, then this can be achieved using p1820 (direction of rotation reversal).
Description: Sets the signal source for the control command to the bypass.
Dependency: The "Bypass" function is only available for induction motors.
Description: Sets the cause that should initiate the bypass.
Dependency: The "Bypass" function is only available for induction motors.
p1263 Debypass delay time / Debypass t_del
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.000 [s] 300.000 [s] 1.000 [s]
p1264 Bypass delay time / Bypass t_del
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.000 [s] 300.000 [s] 1.000 [s]
p1265 Bypass speed threshold / Bypass n_thresh
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: p2000 Dyn. index: -
Unit group: 3_1 Unit selection: p0505 Func. diagram: -
Min Max Factory setting
0.00 [rpm] 210000.00 [rpm] 1480.00 [rpm]
p1266 BI: Bypass control command / Bypass command
Access level: 2 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0
p1267 Bypass changeover source configuration / Chngov_src config
Access level: 2 Calculated: - Data type: Unsigned8
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Bypass via signal (BI: p1266) Yes No -
01 Bypass via reaching the speed threshold Yes No -