User Manual
SINAMICS G120 CU230P-2 Control Units
List Manual, 04/2018, A5E33838102
169
2 Parameters
2.2 List of parameters
Description: Sets the initial rounding-off time for OFF3 for the extended ramp generator.
Description: Sets the final rounding-off time for OFF3 for the extended ramp generator.
Description: Sets the signal source for scaling the ramp-up time of the ramp-function generator.
Dependency: Refer to: p1120
Note: The ramp-up time is set in p1120.
Description: Sets the signal source for scaling the ramp-down time of the ramp-function generator.
Dependency: Refer to: p1121
Note: The ramp-down time is set in p1121.
Description: Sets the signal source for the command "enable ramp-function generator/inhibit ramp-function generator".
For the PROFIdrive profile, this command corresponds to control word 1 bit 4 (STW1.4).
BI: p1140 = 0 signal:
Inhibits the ramp-function generator (the ramp-function generator output is set to zero).
BI: p1140 = 1 signal:
Enable ramp-function generator.
Dependency: Refer to: r0054, p1141, p1142
p1136[0...n] OFF3 initial rounding-off time / RFGOFF3 t_strt_rnd
PM330 Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 3070
Min Max Factory setting
0.000 [s] 30.000 [s] 0.500 [s]
p1137[0...n] OFF3 final rounding-off time / RFG OFF3 t_end_del
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 3070
Min Max Factory setting
0.000 [s] 30.000 [s] 0.000 [s]
p1138[0...n] CI: Ramp-function generator ramp-up time scaling / RFG t_RU scal
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: PERCENT Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 3070
Min Max Factory setting
- - 1
p1139[0...n] CI: Ramp-function generator ramp-down time scaling / RFG t_RD scal
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: PERCENT Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 3070
Min Max Factory setting
- - 1
p1140[0...n] BI: Enable ramp-function generator/inhibit ramp-function generator / Enable RFG
CU230P-2_DP
CU230P-2_PN
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 2501
Min Max Factory setting
- - [0] 2090.4
[1] 1
[2] 2090.4
[3] 2090.4