2 Parameters
2.2 List of parameters
Dependency: Refer to: p1055, p1056
Description: Sets the speed for jog 2.
Jogging (JOG) is level-triggered, and allows the motor to be incrementally traversed.
Dependency: Refer to: p1055, p1056
Description: Sets the speed limit effective in the setpoint channel.
Dependency: Refer to: p1082, p1083, p1085, p1086, p1088
Description: Sets the signal source for the main setpoint.
Examples:
r1024: Fixed speed setpoint effective
r1050: Motor. potentiometer setpoint after the ramp-function generator
Dependency: Refer to: p1071, r1073, r1078
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source for the main setpoint.
Examples:
r1024: Fixed speed setpoint effective
r1050: Motor. potentiometer setpoint after the ramp-function generator
Dependency: Refer to: p1071, r1073, r1078
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1059[0...n] Jog 2 speed setpoint / Jog 2 n_set
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dyn. index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Func. diagram: 3001, 3030
Min Max Factory setting
-210000.000 [rpm] 210000.000 [rpm] -150.000 [rpm]
p1063[0...n] Setpoint channel speed limit / Setp_chan n_lim
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Func. diagram: 3040
Min Max Factory setting
0.000 [rpm] 210000.000 [rpm] 210000.000 [rpm]
p1070[0...n] CI: Main setpoint / Main setpoint
CU230P-2_DP
CU230P-2_PN
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2000 Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 3001, 3030
Min Max Factory setting
- - [0] 2050[1]
[1] 0
[2] 0
[3] 0
p1070[0...n] CI: Main setpoint / Main setpoint
CU230P-2_HVAC
CU230P-2_CAN
CU230P-2_BT
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2000 Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 3001, 3030
Min Max Factory setting
- - [0] 755[0]
[1] 0
[2] 0
[3] 0