User Manual
2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
114 List Manual, 04/2018, A5E33838102
Description: Sets the smoothing time constant of the 1st order lowpass filter for the analog outputs.
Index: [0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
[2] = Reserved
Note: AO: Analog Output
T: Terminal
Description: Displays the actual output voltage or output current at the analog outputs.
Index: [0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
[2] = Reserved
Dependency: Refer to: p0776
Note: AO: Analog Output
T: Terminal
Description: Activates the absolute value generation for the analog outputs.
Value: 0: No absolute value generation
1: Absolute value generation switched in
Index: [0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
[2] = Reserved
Note: AO: Analog Output
T: Terminal
Description: Sets the analog output type.
p0776[x] = 1 corresponds to a voltage output (p0774, p0778, p0780 are displayed in V).
p0776[x] = 0, 2 corresponds to a current output (p0774, p0778, p0780 are displayed in mA).
Value: 0: Current output (0 mA ... +20 mA)
1: Voltage output (0 V ... +10 V)
2: Current output (+4 mA ... +20 mA)
p0773[0...2] CU analog outputs smoothing time constant / CU AO T_smooth
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 9572
Min Max Factory setting
0.0 [ms] 1000.0 [ms] 0.0 [ms]
r0774[0...2] CU analog outputs output voltage/current actual / CU AO U/I_outp
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 9572
Min Max Factory setting
- - -
p0775[0...2] CU analog outputs activate absolute value generation / CU AO absVal act
Access level: 2 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 9572
Min Max Factory setting
0 1 0
p0776[0...2] CU analog outputs type / CU AO type
Access level: 2 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 9572
Min Max Factory setting
0 2 0