Table 4-21 Cooling air clearances and additional dimensions
Frame
size
Power Module depth [mm] T1 T2 Cooling air clearances [mm]
1)
Top Bottom Front
FSA …
FSC
171 118 53 80 100 100
1)
The Power Module is designed for mounting without any lateral cooling air clearance. For tolerance
reasons, we recommend a lateral clearance of 1 mm.
Table 4-22 Electrical cabinet cutout and mounting holes
Frame
size
Control cabinet cutout [mm] Fixing/torque [Nm]
a b c d e
FSA 103 106 27 198 88 8 × M5 / 3.5
FSB 148 134 34.5 304 116 8 × M5 / 3.5
FSC 123 174 30.5 365 156 10 × M5 / 3.5
Installing
4.3 Installing Power Modules
Converter with the CU230P-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257946B AF 83