4.3.3 Dimension drawings, drilling dimensions for the PM230 Power Module, IP20
The following dimension drawings and drilling patterns are not to scale.
Frame sizes FSA ... FSC
+HLJKWZLWKRXW
VKLHOGSODWH
:LGWK
'HSWK
6KLHOGSODWH

+HLJKWZLWKRXWVKLHOG
SODWH
:LGWK
'HSWK
&8
23
6KLHOG
SODWH
)6$
&8
23
K F
E
K F
E
)6%)6&
Table 4-5 Dimensions depend on the operator panel (OP) that is inserted
Frame
size
Width
[mm]
Height [mm] Mounting depth in the cabinet with
Control Unit (CU) [mm]
2)
without shield
plate
with shield plate without OP with OP
1)
FSA 73 196 276 224 235
FSB 100 292 370 224 235
FSC 140 355 432 224 235
1)
BOP-2, IOP-2 or blanking cover
2)
Power Module depth without Control Unit: 165 mm
Table 4-6 Drilling dimensions, cooling clearances and fixing
Frame size Drilling dimensions [mm] Cooling air clearances [mm]
1)
Fixing/torque
[Nm]
b h c Top Bottom Front
FSA 62.3 186 6 80 100 --- 2 x M4 / 2.5
FSB 80 281 6 80 100 --- 4 x M4 / 2.5
FSC 120 343 6 80 100 --- 4 x M5 / 3.0
1)
You can mount the Power Modules without any lateral cooling air clearance. For tolerance reasons,
we recommend a lateral clearance of approx. 1 mm.