10.9 Restrictions for special ambient conditions
10.9.1 Permissible line supplies dependent on the installation altitude
Permissible line supplies dependent on the installation altitude
For installation altitudes 2000 m above sea level, it is permissible to connect the inverter
to any of the line supplies that are specified for it.
For installation altitudes 2000 m ... 4000 m above sea level, the following applies:
Connection to a TN line system with grounded neutral point is permissible.
TN systems with grounded line conductor are not permitted.
The TN line system with grounded neutral point can also be supplied using an isolation
transformer.
The phase-to-phase voltage does not have to be reduced.
Note
Using Power Modules connected to TN line supplies with voltages ≥ 600 V for installation
altitudes 2000 m … 4000 m
For voltages 600 V, the TN line supply must have a grounded neutral point established using
an isolating transformer.
Current derating as a function of the installation altitude
The permissible inverter output current is reduced above an installation altitude of 1000 m.
,QVWDOODWLRQDOWLWXGH>P@
2XWSXWFXUUHQW
>@




   
Figure 10-6 Characteristic for PM230 Power Modules, PM250 Power Modules and PM330 Power
Modules, HX and JX
,QVWDOODWLRQDOWLWXGH>P@
2XWSXWFXUUHQW
>@




   
Figure 10-7 Characteristic for the PM330 GX Power Module
Technical data
10.9 Restrictions for special ambient conditions
Converter with the CU230P-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257946B AF 515