Efficiency optimization, method 2
Generally, energy efficiency optimization method 2 achieves a better efficiency than method 1.
We recommend that you set method 2.
,QYHUWHU
7KHUPDOPRWRU
PRGHO
(IILFLHQF\
GHSHQGHQWRQWKH
IOX[
2SWLPXPIOX[
Figure 6-62 Determining the optimum flux from the motor thermal model
Based on its thermal motor model, the inverter continually determines - for the actual operating
point of the motor - the interdependency between efficiency and flux. The inverter then sets
the flux to achieve the optimum efficiency.
)OX[
(IILFLHQF\
)OX[
(IILFLHQF\
(IILFLHQF\RSWLPL]DWLRQLVQRWDFWLYH
(IILFLHQF\RSWLPL]DWLRQLVDFWLYH




Figure 6-63 Qualitative result of efficiency optimization, method 2
Depending on the motor operating point, the inverter either decreases or increases the flux in
partial load operation of the motor.
Efficiency optimization, method 1
)OX[VHWSRLQW
7RUTXH1RORDG
RSHUDWLRQ
5DWHGWRUTXH
3DUWLDOORDGRSHUDWLRQ
Sy
Sy
S
S 
S 
S 
Figure 6-64 Reduce the flux setpoint in the partial load range of the motor
Advanced commissioning
6.35 Efficiency optimization
Converter with the CU230P-2 Control Units
360 Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257946B AF