User Manual

Parameter Description
p2383 Cascade control - deactivation sequence (factory setting: 0)
0: Normal stop
1: Sequential stop:
For OFF1, the inverter deactivates the motors in the following sequence:
M3 → M2 → M1 → controlled motor
p2387 is the time between the deactivations.
p2384 Cascade control - motor switch-on delay (factory setting: 0 s)
p2385 Cascade control - stop time activation speed (factory setting: 0 s)
p2386 Cascade control - motor deactivation delay (factory setting: 0 s)
p2387 Cascade control - stop time deactivation speed (factory setting: 0 s)
See p2383
For more information, see the parameter descriptions and function diagram 7036 in the List
Manual.
Advanced commissioning
6.20 Cascade control
Converter with the CU230P-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257946B AF 299