User Manual
An overview of all the parameters that belong to the command data sets is provided in the List
Manual.
Note
It takes approximately 4 ms to toggle between command data sets.
Changing the number of command data sets
Procedure
1. Set p0010 = 15.
2. The number of command data sets is configured with p0170.
3. Set p0010 = 0.
You have changed the number of command data sets.
❒
Copying command data sets
Procedure
1. Set p0809[0] to the number of the command data set whose settings you wish to copy
(source).
2. Set p0809[1] to the number of the command data set in which you wish to copy the settings.
3. Set p0809[2] = 1
4. The inverter sets p0809[2] = 0.
You have copied the settings of a command data set into another command data set.
❒
Parameter
Parameter Description
p0010 Drive commissioning parameter filter
r0050 Command data set CDS active
Displays the number of the currently active command data set
p0170 Number of command data sets (CDS) (factory setting: 2)
p0170 = 2, 3 or 4
p0809[0] Copying the command data set CDS (factory setting: 0)
[0] Source command data set
[1] Target command data set
[2] 0→1: Starts the copy operation
p0810 Command data set selection CDS bit 0
p0811 Command data set selection CDS bit 1
Advanced commissioning
6.12 Switching over the drive control (command data set)
Converter with the CU230P-2 Control Units