User Manual
Adapting the characteristic
You must define your own characteristic if none of the default types match your particular
application.
Application example
The inverter should convert a 6 mA … 12 mA signal into the value range ‑100 % … 100 % via
analog input 0. The wire break monitoring of the inverter should respond when 6 mA is fallen
below.
&XUUHQWLQSXWP$P$
[
S
\
S
[
S
\
S
P$
Figure 6-7 Characteristic for the application example
Procedure
1. Set the DIP switch for analog input 0 on the Control Unit to current input ("I"):
, 8
2. set p0756[0] = 3
You have defined analog input 0 as current input with wire break monitoring.
3. Set p0757[0] = 6.0 (x1)
4. Set p0758[0] = -100.0 (y1)
5. Set p0759[0] = 12.0 (x2)
6. Set p0760[0] = 100.0 (y2)
7. Set p0761[0] = 6
An input current < 6 mA results in fault F03505.
The characteristic for the application example is set.
❒
Advanced commissioning
6.3 Adapt the default setting of the terminal strip
Converter with the CU230P-2 Control Units
210 Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257946B AF