Application:
[0]: In all applications that do not fall under [1] … [3]
[1]: Applications involving pumps and fans
[2]: Applications with short ramp-up and ramp-down times. However, this setting is not
suitable for hoisting gear and cranes/lifting gear.
[3]: Setting only for steady-state operation with slow speed changes. We recommend
setting [1] if load surges in operation cannot be ruled out.
Motor identification:
[1]: Recommended setting. Measure the motor data at standstill and with the motor rotating.
The inverter switches off the motor after the motor data identification has been completed.
[2]: Measure the motor data at standstill. The inverter switches off the motor after the motor
data identification has been completed.
Recommended setting for the following cases:
You have selected "Speed control" as control mode, however the motor cannot freely
rotate, e.g. for mechanically limited traversing sections.
You have set "V/f control" as control mode.
[3]: Measure the motor data while the motor is rotating. The inverter switches off the motor
after the motor data identification has been completed.
[11]: The same setting as [1]. The motor accelerates to the currently set setpoint after the
motor data identification.
[12]: The same setting as [2]. The motor accelerates to the currently set setpoint after the
motor data identification.
Calculating the motor parameters: Select "Complete calculation".
Set the check mark for "RAM data to EEPROM (save data in the drive)" to save your data in
the inverter so that it is not lost if the power fails.
Press the "Finish" button.
You have entered all of the data that is necessary for the quick commissioning of the inverter.