User Manual
Default setting 114: "P1 fieldbus"
$FNQRZOHGJHIDXOW
&RQWUROYLDILHOGEXV3EDXG
6SHHGDFWXDOYDOXH
&XUUHQWDFWXDOYDOXH
$ODUP
)DXOW
',
$2
$2
'2
'2
DO 0: p0730, …, DO 2: p0732 AO 0: p0771[0], AO 1: p0771[1] DI 2: r0722.2
Designation in the BOP-2: p_f_P1
Default setting 120: "PID settings for pumps and fans"
The default setting restores the function of the terminal strip to the factory setting.
Technology controller setting:
● Ramp-up/down time for setpoint: p2257 = p2258 = 30 s
● Ramp-up/down time for controller output: p2293 = 30 s
● Actual value upper limit: p2267 = 120%
● Actual value filter time constant: p2265 = 10 s
Designation in the BOP-2: P_F_PID
Default setting 200: "Option L13, main contactor"
The macro is intended for the G120P Cabinet with option L13 (main contactor).
0DLQFRQWDFWRUFRQWURO
'2
DO 2: p0732
Designation in the BOP-2: L13
Default setting 201: "Option L57, L59, L60, Emergency Stop"
The macro is intended for the G120P Cabinet with options L57, L59 and L60 (Emergency Stop).
2))
2))
',
',
DI 4: r0722.4, DI 5: r0722.5
Designation in the BOP-2: L57_60
Installing
4.5 Connecting the interfaces for the inverter control
Converter with the CU230P-2 Control Units
136 Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257946B AF