4.5 Supported objects
Fieldbuses
Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
89
Table 4- 4 Instance Attribute
No.
Service
Type
Name
Value/explanation
1
get
UINT16
Vendor ID
1251
2 get UINT16 Device Type
- ODVA AC Drive
- Siemens Drive
02 hex
12 hex
3
get
UINT16
Product code
r0964[1]
4
get
UINT16
Revision
The versions should match the EDS file
5
get
UINT16
Status
See the following table
6 get UINT32 Serial number bits 0 … 19: consecutive number;
bits 20 … 23: Production identifier
bits 24 … 27: Month of manufacture (0 = Jan, B =
Dec)
Bits 28 … 31: Year of manufacture (0 = 2002)
7 get Short
String
Product name max. length 32 bytes
e.g. SINAMICS G120
Table 4- 5 Explanation of No. 5 of the previous table
Byte
Bit
Name
Description
1 0 Owned 0: Inverter is not assigned to any master
1: Inverter is assigned to a master
1
Reserved
2 Configured 0: Ethernet/IP basic settings
1: Modified Ethernet/IP settings
For G120, always = 1
3
Reserved
4 … 7 Extended De-
vice Status
0: Self-test or status not known
1: Firmware update active
2: At least one I/O connection with error
3: No I/O connections
4: Incorrect configuration in the ROM
5: Fatal fault
6: At least one I/O connection is active
7: All I/O connections in the quiescent state
8 … 15: Reserved
2
8 … 11
Not used
12 … 15
Reserved