User Manual

Communication via PROFIBUS and PROFINET
3.6 Communication via PROFINET
Fieldbuses
Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
69
Get_Measurement_Values
The command returns the requested measured value using the measured value ID
Get_Measurement_Values_with_object_number
The command returns the requested measured values using the measured value ID and
the object number. The object number corresponds to the drive object ID.
Error values
Table 3- 15 Error values in the parameter response
Error
value 1
Meaning
001 hex
Invalid Service_Request_ID
03 hex
Invalid Modifier
04 hex
Invalid Data_Structure_Identifier_RQ
06 hex
No PE energy-saving mode supported
07 hex
Response too long
08 hex
Invalid Block Header
50 hex
No suitable energy-saving mode available
51 hex
Time is not supported
52 hex
Impermissible PE_Mode_ID
53 hex
No switch to energy saving mode because of state operate
54 hex
service or function temporarily not available