User Manual

Communication via AS-i - only for G110M
7.3 Dual Slave mode
Fieldbuses
222 Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
Default setting 31, slave 1 with profile 7.A.5: Control -> inverter
AS-i.DO0
-
>
Time signal for the CTT2 transfer from the AS
-i master
AS-i.DO1
-
>
Data bit for the CTT2 transfer, four bytes cyclically or acyclically via
PIV. The reading and writing of parameters is possible via the PIV.
Because data is transferred bit
-by-bit, the read and write process is
very slow.
AS-i.DO2
-
>
p0881 = 2093.4
Override quick stop
AS-i.DO3
-
>
Select slave A or slave B, interconnected internally
Default setting 31, slave 1 with profile 7.A.5: Inverter -> control
p2080[4] = 722.2
State DI2
-
>
AS
-i.DI0
p2080[5] = 722.3
State DI3
-
>
AS
-i.DI1
Serial data transfer CTT2, four bytes cyclically or acyclically via PIV.
The reading and writing of parameters is possible via the PIV.
Because data is transferred bit-by-bit, the read and write process is
very slow.
-
>
AS
-i.DI2
Time signal for the CTT2 transfer to the AS-i master
-
>
AS
-i.DI3
Default setting 34: Dual Slave mode with setpoint via AS-i field bus
The control accesses the two slaves of the inverter each via four bits.
Via slave 2, in accordance with profile 7.A.E, the control specifies the commands listed
below (AS-i.DO0 … AS-i.DO2).
Via slave 1, the control sends the command for quick stop and the data in cyclical or
acyclical mode.
The control requires one bit per slave in order to specify the slave.
Default setting 34, slave 2 with profile 7.A.E: Control -> inverter
AS-i.DO0
-
>
ON / OFF 1
AS-i.DO1
-
>
OFF 2
AS-i.DO2
-
>
Acknowledge fault
AS-i.DO3
-
>
Select slave A or slave B, interconnected internally
If the control specifies the speed setpoint, the inverter replies:
Default setting 34, slave 2 with profile 7.A.E: Inverter -> control
p2080[0] = 53.13
PLC ready to switch on
-
>
AS
-i.DI0
p2080[1] = 899.11
Pulses enabled
-
>
AS
-i.DI1
p2080[2] = 722.0
State DI0
-
>
AS
-i.DI2
p2080[3] = 722.1
State DI1
-
>
AS
-i.DI3