User Manual
Communication via RS485
5.5 Communication via BACnet MS/TP - only CU230P-2 HVAC / BT
Fieldbuses
Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
157
Instance
ID
Object name
Description
Unit
Range
Access
type
Parameter
AV17 FREQ SP PCT Setpoint 1 (when controlling via
BACnet)
% -199.99 … 199.99 C HSW
AV18 ACT FAULT Number of the fault due to be
dealt with
--- inverter-dependent R r0947[0]
AV19
PREV FAULT 1
Number of the last fault
---
inverter-dependent
R
r0947[1]
AV20
PREV FAULT 2
Number of the fault before last
---
inverter-dependent
R
r0947[2]
AV21 PREV FAULT 3 Number of the fault third from
last
--- inverter-dependent R r0947[3]
AV22 PREV FAULT 4 Number of the fault fourth from
last
--- inverter-dependent R r0947[4]
AV25 SEL STPT Command to select the setpoint
source
--- 0 … 32767 W p1000
AV28
AO1 ACT
Signal from AO 1
mA
inverter-dependent
R
r0774.0
AV29
AO2 ACT
Signal from AO 1
mA
inverter-dependent
R
r0774.1
AV30
MIN Speed
Minimum speed
RPM
0.000 – 19500,000
W
p1080
AV31 MAX Speed Maximum speed RPM 0.000 … 210000.00
0
W p1082
AV32
ACCEL TIME
Ramp-up time
s
0.00 … 999999.0
W
p1120
AV33
DECEL TIME
Ramp-down time
s
0.00 … 999999.0
W
p1121
AV34
CUR LIM
Current limit
A
inverter-dependent
R
p0640
AV39 ACT WARN Indication of a pending alarm --- inverter-dependent R r2110[0]
AV40
PREV WARN 1
Indication of the last alarm
---
inverter-dependent
R
r2110[1]
AV41 PREV WARN 2 Indication of the last but one
alarm
--- inverter-dependent R r2110[2]
AV5000 RAMP UP TIME Technology controller ramp-up
time
s 0 … 650 W p2257
AV5001 RAMP DOWN TIME Technology controller ramp-
down time
s 0 … 650 W p2258
AV5002 FILTER TIME Technology controller actual
value filter time constant
s 0 … 60 W p2265
AV5003 DIFF TIME Technology controller differenti-
ation time constant
s 0 … 60 W p2274
AV5004 PROP GAIN Technology controller propor-
tional gain
s 0 … 1000 W p2280
AV5005 INTEG TIME Technology controller integral
time
s 0 … 1000 W p2285
AV5006 OUTPUT MAX Technology controller maximum
limiting
% - 200 … 200 W p2291
AV5007 OUTPUT MIN Technology controller minimum
limiting
% - 200 … 200 W p2292
AV5100 RAMP UP TIME 0 Technology controller 0 ramp-up
time
s 0 … 650 W p11057
AV5101 RAMP DOWN TIME 0 Technology controller 0 ramp-
down time
s 0 … 650 W p11058
AV5102 FILTER TIME 0 Technology controller 0 actual
value filter time constant
s 0 … 60 W p11065