User's Manual

Siemens PLT 111 · 1999
4/10
I/O modules
Modules which can be used on the I/O bus
Configuring
Designation Order No. of
module
Release Re-
marks
Analog calculation modules
Analog calculation module
6DS1 715-8BB 2
SW:03
Binary calculation modules
Binary calculation module
6DS1 717-8AA 8
SW:08
16)
Binary/analog calculation
module (max. 31 channels)
6DS1 717-8RR 1
SW:3
Binary extension 6DS1 719-8AA 2 15)
Analog extension
6DS1 720-8AA =1 15)
Binary extension
(for 6DS1717-8RR)
6DS1 719-8RR 1
Coupling modules
Speed controller
6DS1 303-8AA 9
Field multiplexer FM 6DS1 304-8AA 6
SW: 2
1)
6DS1 304-8BB 1
SW: 2
1)
S5-110 coupling
6DS1 310-8AA 8
6DS1 310-8AB 8
S5 coupling, serial 6DS1 318-8AB 3
SW: 1
1)
S5 coupling, expansion unit
6DS1 321-8AA 4
S5 coupling, serial 6DS1 333-8AB 1
SW=1
S7 coupling, serial 6DS1 333-8AB 1
SW=1
22)
MODBUS coupling
(on request)
6DS1 333-8AB
with M1328-V5
1
SW=5
3)
I/O bus remote coupling
AS - I/O bus - ES 100 K
6DS1 322-8AA 5 1) 12)
Coupling of SIPART DR20,
TELEPERM D compact
controller
6DS1 325-8AA 2 2) 3)
S5 coupling, serial,
ET100, EU / I/Os, coupling
module TM-S5
6DS1 327-8AA 4
Serial coupling, 4 channels,
hardware without firmware
6DS1 328-8AA 2 18)
TM/EA coupling, I/O bus
6DS1 312-8BB 2 10)
Coupling of external computer
CS 275 / N-V.24
6DS1 202-8AB 5 19) 20)
CP 581 TM interface modules
CP 581 TM communications
module
6DS1 337-1AD
with S5KE,
S5KS
1
SW: ...
19) 20)
2) 21)
CP 581 TM-L2 (DP/FDL)
6DS1 341-1AD
with DP drivers
1
SW: ...
19) 20)
2) 21)
CP 581 TM-L2 (FMS)
6DS1 341-1BD
with S5KE,
S5KS
1
SW: ...
19) 20)
2) 21)
CP 581 TM FUZZY
6DS1 342-1BD
with S5KE,
S5KS
1
SW: ...
19) 20)
2) 21)
Explanations for the column "Remarks"
1) Earlier release versions not permissible!
2) Special product
3) Not a standard product, no system test carried out
4) Cannot be operated in AS 235 systems with auxiliary driver
5) Application only without interrupt!
6) No application as common alarm module (SF 61)
7) Approved for common alarm modules, the latest product release is
required.
8) Note current balance of subrack:
max. 4 A per module, max. 16 A per subrack
9) Combination modules for use in TELEPERM M standard systems and
in TELEPERM ME systems. Application in AS 235 extension units
only as TELEPERM ME module with slot addressing.
10) AS 235: with release 2,
AS 235 H and AS 235 K: with release 1.
11) With AS 235 H: > 5.
12) Observe cycle time for processing with ES 100 K!
(delay resulting from cable lengths)
13) Application in ES 100 K not allowed (timing)
14) Connection of transmitters with two-wire system not permissible with
AS 235 K and ES 100 K in AC 230 V! The ripple of the power supply
in the AS is too high for these transmitters and the connection sys-
tem.
15) Module only functions together with 6DS1 717-8AA
16) Only alarm function
17) Module only functions together with 6DS1 713 or 6DS1 731.
18) Only a hardware module; no function in delivered state. For use with
standard drivers, the module firmware is usually adapted to existing
drivers.
19) A maximum of two modules of type N-V.24 or CP 581 TM are permis-
sible in a system (in basic cabinet and extension cabinet)
20) Application in ES 100 K not allowed (5 V power)
21) Hardware/software releases on request:
Siemens Karlsruhe, Dept. ATD TD 4, D-76181 Karlsruhe
22) S7 coupling with 3964 R / RK 512 procedure,
SEND/RECEIVE, no FETCH, SIMATIC S5 analog value format
Explanations for the column "Release"
5 Tested with AS 235 system technology, no imperative release ver-
sion. No negative information with earlier releases.
1; 2; Permissible releases
=5 Valid release of a module
6 and remark 1) mean an imperative minimum release (6 in this
case), i.e. upgrading is essential at least up to release 6.
Observe the respective indexed remarks for the individual
modules.
This catalog is out of date, see note on page 1