Monitored start - monitor input
Icon
Functional device Monitored start - monitor input
Parameter
Name: max. 29 ASCII characters plaintext
Input mask
Description
The "monitored start - monitor input" start device requires as additional start condition the ac-
tivation of the start input of the corresponding OSSD. If the AND link of all monitoring, logic and
EDM devices of an OSSD returns the result ON and the start condition is fulfilled, the "monito-
red start - monitor input" start device passes on the validation request to the output device.
Configuration log
Type Designation in the configuration log
82 manual start monitor input
Variants
none
Note
Between the occurrence of the ON state of the AND link of all monitoring, logic and EDM de-
vices of an OSSD and the activation of the start input, at least 50ms must pass. The start input
must be activated at least 50ms and at most 2s. 50ms after deactivation of the input, the va-
lidation request is performed.
Example:
0115 INDEX: 47 = "Name"
0116 TYPE: 82 = manual start monitor input
0117 ASSIGNED: channel one