Poster

NCC: Export graphics from NCC
2
NCC: Import the graphics into
Cerberus DMS
3
Part number
Cerberus DMS
Compact
Cerberus DMS
Standard
Feature set & options
Compact feature set (CCA-CMPT-DMS) P55802-Y110-A100 Included
Standard feature set (CCA-STD-FSET) P55802-Y114-A100 Included
Summary Bar & Event List, Journaling, Macros, Time-based Reactions, Scheduler,
Long-Term Storage, Reports, Standard Drivers (BACnet, OPC DA, Modbus, SNMP)
Included Included
Graphic Viewer Included Included
Graphics Editor (CCA-OP-GRAPH-ED) P55802-Y127-A300 + Included
Remote Notication (E-mail, pager, text message) Included Included
Assisted Treatment Included Included
Mobile App and Web Service Connections Included (max. 5) Included
Scripting Engine and Event/value-based Reactions Included
Log Viewer Included
Distributed Systems Included
Upsell license to convert Cerberus DMS Compact License to Standard License (CCA-CMPT-DMS-U) P55802-Y110-A500 +
OPC DA Server Included
Clients
Clients Included 3 (max. 3) 1
Add 1 client (CCA-1-CL) P55802-Y119-A200 +
Add unlimited clients (CCA-MAX-CL) P55802-Y120-A200 +
Fire
Included fire points 500 (max. 2,000) None
Add 100 fire points (CCA-100-FIRE) P55802-Y158-A412 + +
Add 500 fire points (CCA-500-FIRE) P55802-Y158-A452 + +
Add 5,000 fire points (CCA-5000-FIRE) P55802-Y158-A453 +
Add 10,000 fire points (CCA-10000-FIRE) P55802-Y158-A414 +
Video
Included video cameras None (max. 128) None
Video option for external VMS integration Included Included
Video option for embedded VMS (CCA-V-PLUS)
[includes Siveillance VMS 200 embedded, 8 monitors, & 8 embedded camera]
P55802-Y159-A300 + +
Add 16 external cameras (CCA-V-16EXTC) P55802-Y161-A401 + +
Add 128 external cameras (CCA-V-128EXTC) P55802-Y161-A412 + +
Add 16 embedded cameras (CCA-V-16EMBC) P55802-Y162-A401 + +
Add 16 monitors (CCA-V-16MON) P55802-Y160-A401 + +
Add 128 monitors (CCA-V-128MON) P55802-Y160-A412 + +
Step 4a: Computer packages
Selection guide
UL/ULC HW category A computer, 22” LCD monitor, SNC card,
(no software licenses included) – (UHW-CATA-PKG-SM)
S54465-C82-A1
Client, Small server (up to 8,000 points),
Small FEP (max. 2 SNC cards)
*Not recommended as Video Surveillance Client
UL/ULC HW category B computer, 22” LCD monitor, SNC card,
(no software licenses included) – (UHW-CATB-PKG-SM)
S54465-C82-A2
Medium server (up to 19,000 points),
Client, Large FEP (max. 4 SNC cards)
UL/ULC HW category B computer, 42” LCD monitor, SNC card,
(no software licenses included) – (UHW-CATB-PKG-LM)
S54465-C83-A1
Step 4b: Build your own package
Select a computer Selection guide
UL/ULC HW category A computer, Windows 10, SNC card,
Management Station Utility, (No Monitor, or software licenses included)
– (UHW-CATA-01)
S54465-C73-A1
Client, Small server (up to 8,000 points),
Small FEP (max. 2 SNC cards)
*Not recommended as Video Surveillance Client
UL/ULC HW category B computer, Windows 10, SNC card,
Management Station Utility, (No Monitor, or software licenses included)
– (UHW-CATB-01)
S54465-C73-A2
Medium server (up to 19,000 points),
Client, Large FEP (max. 4 SNC cards)
UL/ULC HW category C computer, Windows Server 2016, SNC card,
Management Station Utility, (No Monitor, or software licenses included)
– (UHW-CATC-01)
S54465-C74-A1 Large server (up to 42,000 points)
UL/ULC HW category D computer, Windows Server 2016, SNC card,
Management Station Utility, (No Monitor, or software licenses included)
– (UHW-CATD-01)
S54465-C74-A2 Extra large server (up to 66,000 points)
Select a monitor
UL/ULC 22” LCD Monitor, desktop mount – (UHW-0000-22L-L) S54465-C8-A2
UL/ULC 42” LCD Monitor, wall mount – (UHW-0000-42L-L) S54465-C9-A2
Network interfaces
Selection guide
Serial Network Card interface (XNET) between management station
and Cerberus PRO Modular, FireFinder XLS, and MXL – (SNC)
S54400-N1-A1
One SNC is provided with each UL/ULC listed
computer. Select if multiple XNET fire net-
works need to be connected to a server/FEP.
Monitoring Only interface (XNET) between management station
and Cerberus PRO Modular, FireFinder XLS, and MXL – (MOSA)
S54465-C62-A1
Select the MOSA for monitoring only
applications using non-UL/ULC listed
computers.
Network switches
Selection guide
Multi-mode fiber ethernet switch. UL listed – (Scalance X204-2) 500-650537
Use two switches to connect 1) clients,
or 2) Cerberus PRO panels to the server.
For UL applications, select the
Scalance X204-2 or Scalance X204-2LD
Ethernet switches.
Single-mode fiber ethernet switch. UL listed – (Scalance X204-2LD) S54430-A6-A1
Ethernet switch (modular) with CAT5, Multi-mode, and Single-Model
Ethernet module options. UL & ULC listed – (FN2012-A1)
S54400-B152-A1
Use two switches to connect 1) clients,
or 2) Cerberus PRO panels to the server.
For ULC applications, select the Ethernet
switch (modular) FN2012-A1 and appropriate
Ethernet modules (VN2001-A1, VN2002-A1,
VN2003-A1).
Note: This switch can be used for
UL applications, however, the Scalance
X204-2/X204-2LD switches are recommended
for UL applications.
Electric/CAT5 Ethernet module for modular Ethernet switch
(FN2012-A1). UL & ULC listed – (VN2001-A1)
S54400-A42-A1
Multi-mode fiber Ethernet module for modular Ethernet switch
(FN2012-A1). UL & ULC listed – (VN2002-A1)
S54400-A43-A1
Single-mode fiber Ethernet module for modular Ethernet switch
(FN2012-A1). UL & ULC listed – (VN2003-A1)
S54400-A44-A1
Hospital
Estimating a project
University campus
Building your Cerberus DMS Management Station
Addressing your immediate system needs & accommodating for the future
Cerberus PRO FC922/924 Monitoring-Only Solution
UL864 Listed Equipment
Cerberus PRO FC922/924 and Cerberus PRO Modular panels
connected to same Cerberus DMS
Cerberus PRO FC922/924 and Cerberus PRO Modular panels
connected to the same Cerberus DMS
Start with monitoring only and move to full command & control when customer needs expand!
1. Upgrade to UL/ULC server (and clients).
2. Cerberus PRO FC922/924 – add additional switch and use dedicated fiber between switches.
3. Cerberus PRO Modular – use dedicated copper or fiber with fiber interface modules between server interface card and NIC-C card.
Cerberus Pro Modular (also FireFinder XLS & MXL)
UL864 Listed Equipment
Monitoring only solutions
Cerberus DMS Server & Client
non-UL/ULC Hardware Monitoring-Only
Command & Control
Command & Control
Siemens Scalance
X204-2
XNET Monitoring-Only
Solution Assembly
Cerberus Pro
FC922/924 Panels
Cerberus DMS monitoring-only solutions
Provide the capability to monitor one or more fire panels using the building network infrastructure and commercial-off-the shelf computers
Reduce the cost entry point while providing site-wide situational awareness capabilities and event notifications
Provide an entry point to a management station that can grow in size and capability as customer needs expand
More information at: http://www.brainshark.com/siemenscorp2/CDMS-Monitoring-Only-Solutions/
Cerberus Pro Modular
(also FireFinder XLS & MXL)
XNET
Migration of NCC and MM8000 projects to Cerberus DMS is simple.
Cerberus DMS provides conversion tools from where it is possible to import
MM8000 Composer projects or NCC exported graphics.
Migration tools available from:
NCC v8.x and earlier – If migrating NCC graphics, older versions have to be first
upgraded to NCC v8.0.
MM8000 MP4.50 onward – Older versions have to be first upgraded to MM8000 MP4.50
or newer in order to migrate to Cerberus DMS.
Geographical trees and graphics after migration
Cerberus DMS
Cerberus DMS migration for NCC and MM8000
Smooth migration with NCC and MM8000 conversion tools
Import configuration file of
subsystems into Cerberus DMS
MM8000: Import MM8000 Composer
backup file into Cerberus DMS
2
MM8000: Select the geographical trees and
graphics to be converted
3
1
MM8000
License options Orderable licenses Part number (SSN)
Option 1 – engineering licenses
Time-limited (12 months), renewable licenses
Only available as “dongle-based”
All Cerberus DMS software features for all versions (size and options) are enabled
CMD.04 LMS Micro Dongle
Physical license key for Cerberus DMS (CMD.04 Micro Dongle)
S55802-Y148
CCA-ENG CC engineering
CC engineering license for 12 months
P55802-Y130-A100
Option 2 – startup license
Valid for two months – extendable for an additional month
Only available without dongle
All option features are enabled excluding the size features; to activate the size features,
the customer license is needed
CCA-STARTUP-BASE P55802-Y131-A100
Option 3 – demo license
Valid for 12 months
Standard feature set with all options included
Includes 2 clients, 50 fire data points, 100 SCADA data points, 50 security data points,
16 external doors, 8 monitors, 8 external and embedded cameras
External systems such as SiPass and VMS are not included
CCA-DEMO P55802-Y140-A100
License model to support migration
The migration program gives customers the option to move a site from an older management station from Siemens to Cerberus DMS at an attractive discount rate.
There are two discount policies that can be applied based on the type and version of the legacy system to be migrated.
Product/service Available for
Privileged Software Migration (PSM) NCC v7.81 and higher MM8000 v4.80 and higher MM8000 project with umbrella contract
Standard Software Migration (SSM) Any older version of NCC Any older version of MM8000 LMS modular (all versions)
Understand customer needs
Provide maintenance staff a place a central place to Command &
Control the fire system in an efficient manner.
Provide key personal fire system notifications while onsite or at home.
Site graphics are not needed.
Identify systems to integrate & point count
6 networked Cerberus PRO modular panels
Total of 1423 addressable fire points (detectors, pull stations, I/Os)
Determine the hardware and software characteristics
1x – Cerberus DMS compact feature set (CCA-CMPT-DMS)
2x – License for 500 fire points (CCA-500-FIRE)
1x – Cerberus DMS Computer Package with 22” monitor (UHW-CATA-PKG-SM)
Understand customer needs
Manage multiple systems in a uniform way across a geographically extended area
Provide maintenance staff a place a central place to manage the fire system and monitor several
restricted access areas with video feeds.
Provide key personal fire system notifications while onsite
Identify systems to integrate & point count
10 networked Cerberus PRO Modular panels (Command & Control)
4 networked Cerberus PRO panels (Command & Control)
1 remote stand-alone Cerberus PRO Modular panel (Monitoring-only)
Total of 9,130 addressable fire points (detectors, pull stations, I/Os)
5 video cameras
Determine the hardware and software characteristics
1x – Cerberus DMS feature set (CCA-STD-FSET)
1x – License for 10,000 fire points (CCA-10000-FIRE)
1x – License for Video Option Plus Includes SiVMS 200 embedded, 8 monitors, and 8 embedded camera
licenses (CCA-V-PLUS)
1x – Cerberus DMS Computer Package with 22” monitor (UHW-CATB-PKG-SM)
1x – XNET Monitoring-only interface (MOSA)
1x – UL-listed Ethernet switch, multi-mode fiber (Scalance X204-2)
Cerberus PRO Modular
(also FireFinder XLS & MXL)
UL864 Listed Equiqment
Cerberus Pro FC922/924 Panels
Cerberus PRO Modular
(also FireFinder XLS & MXL)
UL864 Listed Equipment
Siemens Scalance
X204-2 Cerberus Pro FC922/924 Panels
Enhanced operational capability with Cerberus DMS
Remote notification (email, SMS, mobile app) for enhanced awareness
Remote access for offsite diagnostics
Monitor, command & control multiple fire networks with one system
– Cerberus PRO FC922/924
– Cerberus Pro Modular
– FireFinder XLS
– MXL
Extended site monitoring with multiple XNET connections and monitoring only solutions
Assisted treatment feature to step operators through the procedure to handle an event
This cloud indicates that any
non-UL network component may be used
Cerberus DMS
Server & Client
non-UL/ULC Hardware
Monitoring-Only
XNET Monitoring-Only
Solution Assembly
BUILDING STEP
SUMMARY
1. Select feature
set & options
2. Add additional
clients
3. Add the right
disciplines
4. Select a UL/ULC
computer
5. Select additional
network interfaces
(Optional)
6. Select network
switches (Optional)
Engineering & demo licenses
Siemens
Scalance
X204-2
Included Option/feature included
Option not available/orderable seperately
+ Option available as orderable license
Cerberus DMS
Server & Client
UL/ULC Hardware for
Command & Control
This cloud indicates
that any non-UL network
component may be used
Siemens Scalance
X204-2